430.110

Motor Disconnecting Means — Ampere Rating and Interrupting Capacity

MotorsNEC 2026CEC Equivalent: CEC Rule 28-600

Every motor must have a disconnect — a switch, breaker, or other device that can be used to completely de-energize the motor for service. Section 430.110(A) says this disconnect must be rated at 115% of the motor FLC from the NEC tables (not the nameplate). The 15% safety margin accounts for the fact that switching a motor off under load creates an arc at the contacts, and the disconnect must be robust enough to handle that. For a 10 HP, 230V, 3-phase motor with 28A FLC, the minimum disconnect rating is 28 x 1.15 = 32.2A, which typically means you would select a 60A disconnect (the next commonly available trade size). There is an important alternative: a listed non-fused motor-circuit switch with an HP rating equal to or greater than the motor HP is always acceptable, because the manufacturer has already designed it to handle the 115% requirement internally. For fused disconnects, the fuse size inside is governed by 430.52, not 430.110.

When You Need This

  • Selecting a disconnect switch for a new motor installation — this is often the first piece of hardware you order
  • Replacing a motor and verifying the existing disconnect is still adequately rated
  • Answering exam questions about motor disconnect sizing — the 115% multiplier is a common test item
  • Designing motor control centers where each bucket needs a properly rated disconnect
#

Key Points

1Disconnect must be rated at least 115% of motor FLC from the NEC tables
2Use the NEC table FLC, not the motor nameplate FLA, to calculate disconnect size
3A listed non-fused motor-circuit switch with HP rating >= motor HP is always permitted as an alternative
4For fused disconnects, the disconnect ampere rating is per 430.110, but the fuse size is per 430.52
5The disconnect must be in sight of the motor controller, or the controller disconnect must be lockable per 430.102
6For a torque motor, the disconnect must have an ampere rating of at least 115% of the nameplate current

Common Mistakes

Sizing the disconnect at 100% of FLC instead of 115% — the code requires the 15% safety margin

Using the motor nameplate FLA instead of the NEC table FLC for the calculation

Confusing the disconnect ampere rating with the fuse size — for fused disconnects, these are separate calculations under different code sections

Selecting a disconnect based on HP rating alone without verifying the ampere rating meets the 115% requirement

Exam Tip

The disconnect calculation is straightforward: FLC x 1.15, then select the next standard trade size disconnect. Do not confuse this with the 125% conductor sizing rule (430.22) or the 250% breaker rule (430.52). Each motor circuit component has its own multiplier.

Frequently Asked Questions

Yes, if the breaker is within sight of the motor controller location, it can serve as the disconnect. Many installations use a circuit breaker at the panel as the disconnect, with a separate motor starter providing overload protection near the motor.

Table 430.250 gives an FLC of 28A. The minimum disconnect rating is 28 x 1.15 = 32.2A. Standard disconnect sizes are typically 30A, 60A, 100A, etc. Since 30A is less than 32.2A, you would select a 60A disconnect. Alternatively, you could use a motor-rated switch with a 10 HP or higher rating at 230V.

Inline Tools

Motor FLC Calculator

Look up full-load current for any motor HP and voltage

Related Code Sections

This is an educational summary, not the official code text. The NEC® is a registered trademark and copyright © National Fire Protection Association (NFPA). The CEC is copyright © CSA Group. For official code text, visit nfpa.org or csagroup.org. SparkShift is not affiliated with NFPA or CSA Group.