430.22
Single Motor Branch-Circuit Conductor Sizing
Motors are assumed to be continuous-duty loads, meaning they can run for three hours or more without stopping. When a motor runs continuously, the conductors feeding it build up heat steadily. To provide a thermal safety cushion, the NEC says you need to oversize the wire by 25 percent above what the motor nominally draws. So if Table 430.250 says your 10-HP 3-phase motor draws 14 amps, you need conductors rated for at least 17.5 amps (14 times 1.25). You then go to Table 310.16 and pick a wire size that meets or exceeds that adjusted ampacity. An important detail: you always use the FLC from the NEC tables (per 430.6), never the nameplate value, as the starting point for this calculation.
When You Need This
- Sizing branch-circuit wiring for a new motor installation — this is the very first calculation you do
- Replacing a motor and confirming the existing wiring is adequate for the new unit
- Designing a control panel layout where each motor gets a dedicated branch circuit
- Preparing for an exam question that asks you to size conductors for a single motor circuit
Key Points
Common Mistakes
Multiplying the nameplate FLA by 125 percent instead of using the NEC table FLC value
Forgetting the 125-percent multiplier entirely and just selecting wire based on the raw FLC
Confusing the 125-percent conductor sizing rule with the overload protection sizing, which uses a different percentage and different current value
Not checking terminal temperature limits per 110.14(C) after selecting the wire
Exam Tip
The math is straightforward: FLC from table times 1.25, then pick a wire from 310.16. But the exam may combine this with derating. If the question mentions a hot environment or a crowded conduit, you need to apply derating AFTER the 125-percent calculation.
Frequently Asked Questions
The conductors between the VFD and the motor are typically sized at 125 percent of the motor FLC. The conductors from the supply to the VFD input are sized based on the VFD input current rating, which may differ from the motor FLC.
NEC 430.22 is specifically for a single motor on a branch circuit. If you are running conductors to supply two or more motors, you need to follow 430.24, which says to add 125 percent of the largest motor FLC plus 100 percent of all other motor FLCs.
Inline Tools
Motor FLC Calculator
Look up full-load current for any motor HP and voltage
Related Code Sections
This is an educational summary, not the official code text. The NEC® is a registered trademark and copyright © National Fire Protection Association (NFPA). The CEC is copyright © CSA Group. For official code text, visit nfpa.org or csagroup.org. SparkShift is not affiliated with NFPA or CSA Group.