Box Fill Calculator

Calculate electrical box fill per NEC Article 314.16. Includes conductors, equipment grounds, clamps, and device allowances.

Based on NEC 2023 Article 314.16

Professional Verification Required

This calculator provides estimates for reference purposes only. Results must be verified by a licensed electrician or electrical engineer before any installation.

  • Local codes and AHJ requirements may differ from NEC standards
  • Site conditions, temperature, and installation methods affect sizing
  • Always verify ampacity, derating factors, and conductor sizing in the field

NEC Reference: NEC 2023 Article 314.16

Box Configuration

Click a preset to auto-fill, or configure manually below

or customize
NEC 314.16(B) Rules: Count each conductor as 1×. All grounds together count as 1×. All clamps together count as 1×. Each device/yoke counts as 2×.
NEC 314.16 Quick Reference

Volume Allowances (in³)

#14 AWG:2.00#12 AWG:2.25#10 AWG:2.50#8 AWG:3.00

Counting Rules

  • Each conductor = 1× volume
  • All grounds together = 1×
  • All clamps together = 1×
  • Each device/yoke = 2×