220.12

General Lighting Loads

Load CalculationsNEC 2023CEC Equivalent: CEC Rule 8-200

When you are calculating the total electrical load for a building — whether to size a panel, feeders, or service entrance — you need a starting number for lighting. Instead of counting every fixture, the NEC lets you use a simple multiplier based on the building's square footage and occupancy type. For a house, you multiply the square footage by 3 VA per square foot. For an office, you multiply by 2 VA. For a warehouse, you use a much lower 0.25 VA per square foot. The floor area is calculated from the outside dimensions of the building and includes all habitable floors. For dwelling units, you exclude open porches, garages, and unfinished spaces that cannot be adapted for future use. These numbers represent the minimum general lighting load for your calculations — your actual lighting design may end up using more or less energy, but this is the code-required starting point for sizing the electrical infrastructure.

When You Need This

  • Performing a residential load calculation to size the main service panel and service entrance conductors
  • Calculating the general lighting portion of a commercial load calculation
  • Determining the minimum number of 15-amp or 20-amp lighting circuits needed for a dwelling unit
  • Answering exam questions about load calculations — the VA-per-square-foot values are commonly tested
#

Key Points

1Dwelling units: 3 VA per square foot for general lighting
2Offices: 2 VA per square foot (may vary by code edition — check your adopted version)
3Hospitals: 2 VA per square foot
4Warehouses and storage areas: 0.25 VA per square foot
5Floor area is measured from outside building dimensions
6For dwellings, exclude garages, open porches, and unfinished spaces not adaptable for future use
7These are minimum values for load calculations — actual fixture loads may differ
8Demand factors from Table 220.42 can be applied to reduce the lighting load on feeders and services

Common Mistakes

Using the wrong occupancy type VA value — mixing up the dwelling value with the office or hospital value

Measuring floor area from interior dimensions instead of exterior dimensions

Including garages and porches in the dwelling unit floor area calculation

Treating these values as the actual expected load — they are minimum code values for sizing calculations, not energy estimates

Forgetting that these lighting load values already include a receptacle load allowance for dwellings

Exam Tip

For dwelling units, the key number is 3 VA per square foot. The exam will give you a house dimension and ask for the general lighting load. Multiply exterior square footage (minus excluded areas) by 3. Then remember to add the small-appliance branch circuits (1,500 VA each for kitchen and dining) and laundry circuit (1,500 VA) separately.

Frequently Asked Questions

Yes. The general lighting load of 3 VA per square foot for dwelling units includes general-purpose receptacle outlets. You do not add a separate receptacle load on top of this. However, small-appliance branch circuits (kitchen/dining) and the laundry circuit are added separately at 1,500 VA each.

If the specific occupancy type is not listed, you should use the most closely matching occupancy type or the value specified by the authority having jurisdiction (AHJ). Some jurisdictions adopt amendments that add or modify the table values.

Inline Tools

Dwelling Load Calculator

Calculate residential service load per NEC 220

Related Code Sections

This is an educational summary, not the official code text. The NEC® is a registered trademark and copyright © National Fire Protection Association (NFPA). The CEC is copyright © CSA Group. For official code text, visit nfpa.org or csagroup.org. SparkShift is not affiliated with NFPA or CSA Group.