Dwelling Load Calculator

Calculate residential electrical service size per NEC Article 220. Supports both Standard and Optional calculation methods with NEC 310.12 conductor sizing.

Based on NEC 2023 Article 220, 310.12

Professional Use Only: Verify all results with a licensed electrician before installation.Reference: NEC 2023 Article 220

General Loads (NEC 220.12, 220.52)
sqft
2
Fixed Appliances
VA
VA
VA
VA

*Input Nameplate Ratings (VA or Watts)

High Impact
EV & HVAC
VA
Tip: Use 7200 for a 30A charger, 9600 for 40A, or 11520 for 48A hardwired.
VA
VA
NEC Article 220 Reference

220.12 - General Lighting

Dwelling units: 3 VA per square foot of living space.

220.60 - Noncoincident Loads

Only the larger of heating or cooling load is included.

220.82 - Optional Method

100% of first 10 kVA, 40% of remainder, plus 100% HVAC.

310.12 - Service Conductors

Residential service conductors sized at 83% of rating.