215
Feeders
A feeder is any circuit conductor between the service equipment and the final branch-circuit overcurrent device. In practical terms, the wire running from your main panel to a sub-panel in the garage is a feeder. Article 215 tells you how to size it. Section 215.2(A)(1) establishes the core sizing rule: the feeder conductor ampacity must be at least 125 percent of the continuous load plus 100 percent of the noncontinuous load, based on the terminal temperature rating per 110.14(C). Alternatively, per 215.2(A)(2), the ampacity after all correction and adjustment factors must be at least 100 percent of the total load. You must satisfy both calculations and use whichever requires the larger conductor. The informational note to 215.2(A)(4) recommends — but does not mandate — that feeder conductors be sized so voltage drop does not exceed 3 percent, and that the combined voltage drop of feeder plus branch circuit does not exceed 5 percent. While this is only a recommendation, many inspectors and engineers treat it as a practical design target, and exam questions frequently test it. The feeder neutral must be sized per 220.61 to carry the maximum unbalanced load but must never be smaller than the equipment grounding conductor required by 250.122. Feeder taps — where you tap off a feeder without overcurrent protection at the point of the tap — are governed by the tap rules in 240.21(B), including the 10-foot tap rule, the 25-foot tap rule, and the outside feeder tap rule. These tap rules are among the most heavily tested topics on electrician licensing exams.
When You Need This
- Sizing the feeder conductors and conduit for a sub-panel run to a garage, workshop, barn, or outbuilding
- Calculating the minimum wire size for a feeder serving a commercial sub-panel with a mix of continuous and noncontinuous loads
- Evaluating voltage drop on a long feeder run and determining whether to upsize the conductors
- Applying the 10-foot or 25-foot tap rules when tapping off an existing feeder without adding a new breaker at the tap point
- Studying for the journeyman or master electrician exam — feeder sizing and tap rules are among the most tested topics
Key Points
Common Mistakes
Forgetting the 125-percent multiplier on continuous loads — a 100A continuous load requires a feeder rated for at least 125A, not 100A
Treating the 3-percent and 5-percent voltage drop figures as mandatory code requirements — they are informational notes (recommendations), not enforceable rules
Sizing the feeder neutral the same as the ungrounded conductors when the load is balanced — the neutral only needs to carry the maximum unbalanced load per 220.61
Applying the 25-foot tap rule but forgetting that the tap conductors must have an ampacity of at least one-third the rating of the OCPD protecting the feeder
Not accounting for all correction and adjustment factors (ambient temperature, conduit fill) before comparing to the load — 215.2(A)(2) requires the adjusted ampacity to meet or exceed 100% of the total load
Exam Tip
The exam will test voltage drop numbers: 3% feeder, 2% branch circuit, 5% total. These come from the informational notes in 210.19(A) and 215.2(A)(4). Also know the tap rules cold: 10-foot tap = not less than 1/10 of the OCPD rating, terminates in a single OCPD; 25-foot tap = not less than 1/3 of the OCPD rating, enclosed in raceway, terminates in a single OCPD. The outside tap rule has no length limit but must terminate at a single OCPD immediately upon entering the building.
Frequently Asked Questions
No. The 3-percent feeder voltage drop and 5-percent total voltage drop are informational notes — recommendations, not enforceable requirements. However, most engineers design to these targets, many AHJs expect compliance, and exam questions treat them as gospel. In practice, exceeding 5% total voltage drop causes visible lamp flicker and motor performance issues, so it is a smart design limit.
A feeder runs from the service equipment (or separately derived system) to the final branch-circuit overcurrent device — typically a sub-panel. A branch circuit runs from the final overcurrent device (breaker in the sub-panel) to the outlets or equipment. The feeder feeds the panel; the branch circuit feeds the load. Article 215 covers feeders; Article 210 covers branch circuits.
Yes, under the feeder tap rules in 240.21(B). The most common are the 10-foot tap rule (tap conductors rated at least 1/10 of the OCPD, enclosed in raceway, terminate at a single OCPD within 10 feet) and the 25-foot tap rule (tap conductors rated at least 1/3 of the OCPD, enclosed in raceway, terminate at a single OCPD within 25 feet). The outside tap has no length limit but must enter the building and terminate immediately at an OCPD.
Inline Tools
Wire Size Calculator
Calculate the correct conductor size for any circuit
Related Code Sections
This is an educational summary, not the official code text. The NEC® is a registered trademark and copyright © National Fire Protection Association (NFPA). The CEC is copyright © CSA Group. For official code text, visit nfpa.org or csagroup.org. SparkShift is not affiliated with NFPA or CSA Group.