CEC Rule 14-104

Rating of Overcurrent Devices

Canadian Electrical CodeCEC 2024NEC Equivalent: NEC 240.4

This is Canada's equivalent to NEC 240.4. The core principle is simple: the overcurrent device (OCPD) is there to protect the wire from melting. Therefore, the rating of the trip element or fuse cannot be higher than the steady-state ampacity of the conductor. However, 14-104(a) provides the 'next standard size' exception: if the conductor's ampacity does not correspond to a standard OCPD size (which are listed in Table 13), you are permitted to use the next higher standard size, provided the rating does not exceed 800A. Additionally, Rule 14-104(2) places absolute hard caps on small conductors: 15A max for #14 AWG copper, 20A max for #12 AWG copper, and 30A max for #10 AWG copper. Unlike some other rules, these max breaker sizes are locked in stone for general-purpose circuits.

When You Need This

  • Choosing the right circuit breaker for standard residential branch circuits.
  • Rounding up to the next standard breaker size for feeders.
  • Sizing protection for derated wires where the new ampacity is non-standard.
#

Key Points

1The overcurrent device cannot exceed the conductor's tabulated ampacity (after derating).
2If the ampacity falls between standard sizes (Table 13), you may round up with a maximum of 800A.
3Above 800A, you must round down.
4#14 AWG is capped at a 15A breaker.
5#12 AWG is capped at a 20A breaker.
6#10 AWG is capped at a 30A breaker.

Common Mistakes

Trying to put a 20A breaker on #14 AWG wire because its 90°C rating is higher than 15A (capped at 15A).

Rounding up to the next standard size on a service over 800A (you must round down).

Confusing overload protection limits with short-circuit rules for motors.

Exam Tip

Always verify Table 13 standard sizes before assuming a breaker size exists. Memorize the small conductor limits: 14=15A, 12=20A, 10=30A.

Frequently Asked Questions

Yes, but only in specific scenarios like motor circuits (Rule 28) or A/C equipment where the OCPD acts only as short-circuit protection, not overload protection.

Inline Tools

Circuit Breaker Calculator

Find the correct OCPD size for your circuit

Related Code Sections

This is an educational summary, not the official code text. The NEC® is a registered trademark and copyright © National Fire Protection Association (NFPA). The CEC is copyright © CSA Group. For official code text, visit nfpa.org or csagroup.org. SparkShift is not affiliated with NFPA or CSA Group.