Calculate maximum overcurrent protection device (OCPD) sizes for transformers per NEC 450.3 or CEC Rule 26-254. Supports single-phase and three-phase, supervised and unsupervised locations.
Based on NEC 450.3 / CEC Rule 26-254
When 125% does not correspond to a standard OCPD rating, the next higher standard size is permitted.
Primary FLA
90.21A
125% = 112.77A
Secondary FLA
208.19A
Calculation Breakdown
1.Phase: Three-phase
2.Primary FLA = 75 kVA x 1000 / (480V x 1.732) = 90.21A
3.Secondary FLA = 75 kVA x 1000 / (208V x 1.732) = 208.19A
4.Impedance: 5%
5.Location: Supervised
6.Protection: Primary Only
7.Applying NEC Table 450.3(B) (1000V and below transformers)
8.Impedance <= 6%: Primary max = 125%
9.Note: Next standard size up permitted if 125% does not match a standard OCPD rating
10.Primary max OCPD amps = 90.21A x 125% = 112.77A
11.Primary OCPD: next standard size up = 125A
Per NEC 450.3: Overcurrent protection for transformers. Table 450.3(A) applies to transformers over 1000V; Table 450.3(B) applies to 1000V and below.
IMPORTANT LEGAL DISCLAIMER
For Reference Only: This calculator is provided for educational and informational purposes only. It is not intended to be a substitute for professional engineering design, advice, or certification.
Code Compliance: Calculations are based on the 2023 National Electrical Code (NEC®). However, local codes, amendments, and Authority Having Jurisdiction (AHJ) requirements vary by location and may supersede standard NEC requirements.
Verify with Your AHJ: Local Authority Having Jurisdiction (AHJ) requirements take precedence over all general code references. Contact your local building department or electrical inspector to confirm applicable codes, amendments, and permit requirements before beginning any electrical work.
No Liability: SparkShift, LLC and its affiliates assume no liability for errors, omissions, or the use/misuse of this tool. Users are solely responsible for verifying all results against applicable codes and standards before installation. Always consult a licensed electrician or Professional Engineer (PE).
NEC Reference: NEC 450.3 / CEC Rule 26-254